Description |
|
Reduction
in contact M. V. Drop A |
|
|
|
|
|
|
|
| 1)
Contact Resistances Reduction after conversion from Aluminium
to copper is measured in terms of milivolt drop.
On average on minimum side.This reduction is found
to be 60 MV Per Cell at 35 Ka Load
. |
|
60 MV
|
|
|
|
|
|
| 2)
At full load This drop will be(55 KA/35KA) |
95
MV |
|
|
|
|
|
| 3)
Current thru each set of Busbar |
6110
Amps. |
|
|
|
|
|
| 4)
Power Savings per set per day |
95/1000
X 6110/1000 X24 = 13.93 Kwh |
|
|
|
|
|
| 5)
Power Savings per cell per day |
13.93
X 9 =125 Kwh |
|
|
|
|
|
|
| |
| Description |
Unit |
Copper
Busbars |
Aluminium
Busbars |
|
|
|
|
|
|
| 1)
Total Cell Current |
Amps |
55000 |
55000 |
|
|
|
|
|
|
| 2)
Current per set of busbar(9sec/cell) |
Amps |
6110 |
6110 |
|
|
|
|
|
|
| 3)
Resistivity at 200 Celsius |
Ohm-cm |
1.7241
X 10-6 |
2.8260
X 10-6 |
|
|
|
|
|
|
|
Resistivity at 500 Celsius |
Ohm-cm |
1.7515
X 10-6 |
3.1650
X 10-6 |
|
|
|
|
|
|
|
Resistivity at 800 Celsius |
Ohm-cm |
2.131
X 10-6 |
3.5040
X 10-6 |
|
|
|
|
|
|
| 4)
Operating Temperature of BB |
Deg
C |
50
Max |
80
Average |
|
|
|
|
|
|
| 5)
Resistence at operating |
|
|
|
|
|
|
|
|
|
|
L - Bend ( C - ! ) |
|
1.13
X 10-6 |
2.8260
X 10-6 |
|
|
|
|
|
|
|
L - Bend ( C - ! ) |
|
2.135
X 10-6 |
2.8260
X 10-6 |
|
|
|
|
|
|
|
L - Bend ( C - ! ) Two In parallel |
|
4.312
X 10-6 |
2.8260
X 10-6 |
|
|
|
|
|
|
| 6)
Total Resistivity |
Ohms |
7.577
X 10-6 |
2.8260
X 10-6 |
|
|
|
|
|
|
| 7)
I2R Losses Per Day Per Set |
Kwh |
6.7888 |
13.58 |
|
|
|
|
|
|
| 8)
I2R Losses Per Day Per Cell |
Kwh |
61.10 |
122.22 |