Description
 
Reduction in contact M. V. Drop A
 
1) Contact Resistances Reduction after conversion from Aluminium to copper is measured in terms of milivolt drop.
On average on minimum side.This reduction is found
to be 60 MV Per Cell at 35 Ka Load
.
 



60 MV
2) At full load This drop will be(55 KA/35KA)
95 MV
3) Current thru each set of Busbar
6110 Amps.
4) Power Savings per set per day
95/1000 X 6110/1000 X24 = 13.93 Kwh
5) Power Savings per cell per day
13.93 X 9 =125 Kwh
 
Description
Unit
Copper Busbars
Aluminium Busbars
1) Total Cell Current
Amps
55000
55000
2) Current per set of busbar(9sec/cell)
Amps
6110
6110
3) Resistivity at 200 Celsius
Ohm-cm
1.7241 X 10-6
2.8260 X 10-6
    Resistivity at 500 Celsius
Ohm-cm
1.7515 X 10-6
3.1650 X 10-6
    Resistivity at 800 Celsius
Ohm-cm
2.131 X 10-6
3.5040 X 10-6
4) Operating Temperature of BB
Deg C
50 Max
80 Average
5) Resistence at operating      
    L - Bend ( C - ! )  
1.13 X 10-6
2.8260 X 10-6
    L - Bend ( C - ! )  
2.135 X 10-6
2.8260 X 10-6
    L - Bend ( C - ! ) Two In parallel  
4.312 X 10-6
2.8260 X 10-6
6) Total Resistivity
Ohms
7.577 X 10-6
2.8260 X 10-6
7) I2R Losses Per Day Per Set
Kwh
6.7888
13.58
8) I2R Losses Per Day Per Cell
Kwh
61.10
122.22


[ Home ] [ Copper products ] [ Enquiries ] [ Sitemap ] [ Privacy policy ] [ Resources ]

Electro Copper & Alloys Mfg. Co.

36, Strand Road, 2nd floor, Room #2, Kolkata 700001 INDIA
Phone: +91 (33) 22426154 / 22101495 / 22101496 / 22433040
 Fax:+91 (33) 22431989
email: sales@electrocopperalloys.com

Web Hosting and Designing by eBizindia.com
Search Engine Ranking Optimization by SEOtop10.com